+7 953 733-48-24

The main project according to the original technical specifications

Project BESS 5 MW / ≥15 MWh usable AC energy

Project article: SNEE-5000-3H-LFP

Container LFP complex: approximately 20 MWh nominal capacity for guaranteed output of at least 15 MWh useful AC energy on side 6 kV.

Price under review

There is a comparison of factory offers for architecture 5 MW / about 20 MWh nominal. The final price is fixed after guaranteeing ≥15 MWh useful AC energy for 6 kV, choice of cooling, logistics and Russian installation.

Call Us

Technical data on the original technical specifications

BESS Project Specifications

Each line corresponds to a requirement of the original job. Design values ​​are confirmed by the manufacturer as part of technical and commercial proposal.

Design capacity
no more than 5 MW
Continuous delivery
at least 3 hours at full power
Nominal battery capacity
approximately 20 MWh; confirmed by manufacturer's calculations
Required useful AC energy
at least 15 MWh on side 6 kV with a power of 5 MW
Full charge
no more than 8 hours to 100%
Battery technology
lithium iron phosphate, LFP
Planned depth of discharge
80%, operating range 10–90% SOC
Charge/discharge temperature
0…+55 °C / −20…+55 °C
Self-discharge
less than 3.5% per month
Networking
parallel to existing network 6 kV
Output parameters
49–51 Hz; voltage deviation −15…+10%
PCS overload
105–130% up to 2 minutes; over 200% - 20 ms
Container version
modules of maximum factory readiness, 25 ft HC format according to technical specifications
Shell protection
cable glands IP54, anti-corrosion environment C4, partitions EI 45
packaged transformer substation
6 kV, UHL1, +40…−55 °C, ATS and relay protection
Dispatching
Modbus RTU/TCP, IEC 61850, IEC 60870-5-104
Resource
at least 3000 cycles; capacity at the end of the resource is at least 60%
Service life
BESS at least 20 years; batteries are at least 7 years old
Guarantee
system - 2 years; for individual cabinets and equipment according to technical specifications - up to 5 years

Proposed factory architectures

Two options for 20ft LFP containers

Status: preliminary technical study. The exact model, number of containers and guaranteed energy are fixed in the technical and commercial proposal and the contract.

Basic option for transportation

4×5.0 MWh

≈ 20 MWh nominal

20ft liquid cooled plate containers. Compact delivery scheme; confirmation of ≥15 MWh useful AC energy per 6 kV is required.

High energy alternative

5 × 4.2 MWh

≈ 20.9 MWh nominal

20ft liquid cooled immersion containers. Provides greater energy reserves; the final choice is made after calculating losses, resource and cost.

Acceptance criterion

15 MWh is measured at the 6 kV point of interconnection

The usable energy includes the operating range of the SOC, battery, PCS and transformer losses, HVAC auxiliary needs, temperature reduction and the agreed degradation margin. The nominal capacity of containers in itself does not confirm the fulfillment of the technical specifications.

Compliance with the original technical specifications

Not just a battery container, but a single energy complex

The parameters below have been transferred from the main text and appendices of the technical specifications. The final values ​​are confirmed by the manufacturer's design and proposal.

5 MW

Power conversion

Bi-directional PCS, DC cabinets and battery strings with BMS coordination.

3 hours

Guaranteed issue

Full design power continuously, after an overnight charge of up to 8 hours.

6 kV

Network integration

packaged transformer substation, ATS, relay protection and synchronization by phase, voltage and frequency.

−55 °C

Climatic version

packaged transformer substation UHL1 and engineering container systems for work on industrial sites.

80% DoD

Battery operating range

LFP, 10-90% SOC range, monitoring every storage tier.

3000+

Cyclic resource

At least 3000 cycles with a residual capacity of at least 60% of the initial one.

Contents of the project supply

All subsystems provided for in the technical specifications

packaged transformer substation can be replaced with a transformer as part of the BESS module, if this is confirmed by the design solution.

01

Cumulative part

LFP strings, BMS, parallel string logic control and DC cabinets.

02

Power transformation

Bidirectional PCS, protection, metering and power addition mode when load threshold is exceeded.

03

packaged transformer substation 6 kV

Transformer, one-way service panel, automatic transfer switch, relay protection and automation and auxiliary power supply.

04

Engineering systems

Heating, air conditioning, lighting, auxiliary needs, addressable fire alarm.

05

Control and SCADA

Local control system, event archive and exchange via Modbus and IEC protocols with the upper level.

06

Project and documentation

Detailed design, drawings, passports, certificates, spare parts, factory acceptance and training.

Budget update

Calculation 5 MW / about 20 MWh nominal

The previous guideline of 449.73 million rubles was formed from a base of $3.5 million and was saved only as an early budget estimate. Factory prices are currently being requested for increased capacity and different cooling systems.

The final budget will include confirmed FOB/DDP, component classification, 22% VAT, logistics, certification, Russian installation and commissioning. This is not a public offer.
Early budget estimate
RUB 449.73 million
Nominal capacity
≈ 20 MWh
Useful energy for 6 kV
≥ 15 MWh
Final price
after the technical and commercial proposal
Status
under review

Scalable versions of HELIKOR

1 and 2 MW - not separate positions of the original technical specification

These are commercial options based on the same architecture. Their price is calculated separately taking into account the higher share of fixed project costs.

Design package according to technical specifications

Request a confirmed price and deadline

Together with commercial proposal we will fix the number of containers, brands of cells and PCS, single-line diagram, packaged transformer substation 6 kV, production schedule and delivery conditions.

?HelpAll Products

HELIKOR

Request a quote

Leave your contacts and we will clarify the task, equipment and delivery time.